Full metadata record
DC FieldValueLanguage
dc.contributor.authorSchneider, K.P.-
dc.contributor.authorEngel, D.W.-
dc.contributor.authorChen, Y.-
dc.contributor.authorThompson, S.E.-
dc.contributor.authorChassin, D.P.-
dc.contributor.authorPratt, R.G.-
dc.date.accessioned2017-06-30T17:26:37Z-
dc.date.available2017-06-30T17:26:37Z-
dc.date.issued200-11-
dc.identifier.urihttp://item.bettergrids.org/handle/1001/162-
dc.description.abstractThis model is one of 24 prototypical feeders as well as including limited equipment information. The number of nodes includes only the primary distribution system; there are additional nodes in the secondary system. The secondary system nodes are on the customer side of their service transformer. These are the nodes, and links, that model the connections from the service transformer to the service meters via triplex or other cables. As discussed earlier in section 2.2 the classification process separated the feeders into three voltage classes; 12.47 kV, 25.00 kV, and 35.00 kV. In the actual feeder models it will be seen that voltages other than these three are used. From Tables 3 and 4 it can be seen that within the 12.47 kV cluster there are 12.47 kV and 13.8 kV feeders. This fact is represented in the following feeder descriptions Climate region 5 is the South East of the United States and is characterized by a hot and humid climate. Within climate region 5 there are 5 12.47 kV feeder types, 1 25.00 kV feeder type, and 1 35.00 kV feeder type. This feeder is a representation of a moderately populated suburban area with a lightly populated urban area. This is composed mainly of single family residences with some light commercial loads. Approximately 48% of the circuit-feet are overhead and 52% underground. It would be expected that this feeder has connections to adjacent feeders through normally open switches. For this reason it would be common to limit the feeder loading to 50% to ensure the ability to transfer most of the loads from other feeders, and vice versa. The residential load is spread out across the entire length of the feeder. The primary feeder extends a significant distance before there is any significant load. This is a configuration that can be seen in a well established system when a new feeder must be routed through an existing area in order to reach new load.en_US
dc.publisherPacific Northwest National Laboratoryen_US
dc.titlePNNL Taxonomy Feeders - Region 5 - Feeder 5en_US
dc.title.alternativeRegion 5 - Feeder 5en_US
dc.typeGrid Model Dataseten_US
grid.publisher.urlhttp://www.pnnl.gov/en_US
grid.formatGridLabDen_US
grid.loads8700en_US
grid.feeders450en_US
grid.nodes1075en_US
grid.voltages12.47 kVen_US
grid.climateZonesHot and humiden_US
grid.identifier.urlhttps://sourceforge.net/p/gridlab-d/code/HEAD/tree/Taxonomy_Feeders/R5-12.47-5.glm-
Appears in Collections:Distribution Steady State

File Description Size Format Export Browse
PNNL GridLAB-D Taxonomy Feeder774.22 kBGRIDLAB D
Associated paper6.57 MBAdobe PDF
Edge data in CSV format80.65 kBDAT CSV
Node data in CSV format126.05 kBDAT CSV


User Comments

Average user rating

0.0 / 5

Rating breakdown

5
80% Complete (danger)
0%
4
80% Complete (danger)
0%
3
80% Complete (danger)
0%
2
80% Complete (danger)
0%
1
80% Complete (danger)
0%

Items in BetterGrids are protected by copyright, with all rights reserved, unless otherwise indicated.