Full metadata record
DC FieldValueLanguage
dc.contributor.authorSchneider, K.P.-
dc.contributor.authorEngel, D.W.-
dc.contributor.authorChen, Y.-
dc.contributor.authorThompson, S.E.-
dc.contributor.authorChassin, D.P.-
dc.contributor.authorPratt, R.G.-
dc.date.accessioned2017-06-30T17:25:40Z-
dc.date.available2017-06-30T17:25:40Z-
dc.date.issued2008-11-
dc.identifier.urihttp://item.bettergrids.org/handle/1001/157-
dc.description.abstractThis model is one of 24 prototypical feeders as well as including limited equipment information. The number of nodes includes only the primary distribution system; there are additional nodes in the secondary system. The secondary system nodes are on the customer side of their service transformer. These are the nodes, and links, that model the connections from the service transformer to the service meters via triplex or other cables. As discussed earlier in section 2.2 the classification process separated the feeders into three voltage classes; 12.47 kV, 25.00 kV, and 35.00 kV. In the actual feeder models it will be seen that voltages other than these three are used. From Tables 3 and 4 it can be seen that within the 12.47 kV cluster there are 12.47 kV and 13.8 kV feeders. This fact is represented in the following feeder descriptions Climate Region 2 Climate region 2 is the North Central and North Eastern portions of the United States and is characterized by a cold climate. Within climate region 2 there are 3 12.47 kV feeder types, 1 25.00 kV feeder type, and 1 35.00 kV feeder type. This feeder is a representation of a lightly populated urban area. This is composed of single family homes, moderate commercial loads, light industrial loads, and some agricultural loads. This feeder supplies a college and an airport. Approximately 25% of the circuit-feet are overhead and 75% underground. It would be expected that this feeder is connected to adjacent feeders through normally open switches. For this reason it would be common to limit the feeder loading to 60% to ensure the ability to transfer load from other feeders, and vice versa. The majority of the load is located relatively near the substation.en_US
dc.publisherPacific Northwest National Laboratoryen_US
dc.titlePNNL Taxonomy Feeders - Region 2 - Feeder 1en_US
dc.title.alternativeRegion 2 - Feeder 1en_US
dc.typeGrid Model Dataseten_US
grid.publisher.urlhttp://www.pnnl.gov/en_US
grid.formatGridLabDen_US
grid.loads6050en_US
grid.feeders3500en_US
grid.nodes482en_US
grid.voltages12.47 kVen_US
grid.climateZonesColden_US
grid.identifier.urlhttps://sourceforge.net/p/gridlab-d/code/HEAD/tree/Taxonomy_Feeders/R2-12.47-1.glm-
Appears in Collections:Distribution Steady State

File Description Size Format Export Browse
PNNL GridLAB-D Taxonomy Feeder363.43 kBGRIDLAB D
Associated paper6.57 MBAdobe PDF
Edges in CSV format34.5 kBDAT CSV
Nodes in CVS format54.81 kBDAT CSV


User Comments

Average user rating

0.0 / 5

Rating breakdown

5
80% Complete (danger)
0%
4
80% Complete (danger)
0%
3
80% Complete (danger)
0%
2
80% Complete (danger)
0%
1
80% Complete (danger)
0%

Items in BetterGrids are protected by copyright, with all rights reserved, unless otherwise indicated.